PV1500E-2A
Photovoltaic Fuses
gPV Fuses
The PV1500E Series solar fuse is designed to integrate into an in-line assembly within a wire harness. The PV1500E Capable of withstanding high cycling and low level fault current conditions.
Part Numbering System

Specification
| Part Number | Current Rating (A) |
Voltage Rating | Interrupting Rating | Energy Integrals I²t (A²S) | Power Loss @1.0In (W) | |
|---|---|---|---|---|---|---|
| Pre-Arcing | Total at 1500V | |||||
| PVI500E-2A | 2 | 1500VDC@30kA | 3.5 | 10 | 2.6 | |
| PVI500E-4A | 4 | 15 | 50 | 2.8 | ||
| PVI500E-5A | 5 | 22 | 75 | 3.2 | ||
| PVI500E-10A | 10 | 300 | 1100 | 4.2 | ||
| PVI500E-12A | 12 | 20 | 60 | 4.2 | ||
| PVI500E-15A | 15 | 35 | 95 | 5.0 | ||
| PVI500E-20A | 20 | 115 | 820 | 6.2 | ||
| PVI500E-25A | 25 | 175 | 1300 | 5.7 | ||
| PVI500E-30A | 30 | 241 | 1950 | 7.5 | ||
- DC Interrupting Rating - Measured at designated voltage, time constant < 50 microseconds.
- Typical Melting I2 t measured at 10In Current.
- Typical Voltage Drop measured at rated current after temperature has stabilized.
Dimension
(Unit: mm)
Standard cylindrical, ordering code - PV1500E-xxA ( 2A~15A)

Package/MOQ
PV1500E-xxA: 28pcs fuses in one carton;
PV1500E-xxA-I : 40pcs fuses in one carton.
In-line crimp terminal type, ordering code - PV1500E-xxA-I( 2A~15A)
Note: for 10-12AWG (6-4mm2 ); Recommended Crimping Tool: T&B Sta-Kon ERG4002 or equivalent.
Standard cylindrical, ordering code - PV1500E-xxA ( 20A~30A)

In-line crimp terminal type, ordering code - PV1500E-xxA-I( 20A~30A)

Note: for 10-12AWG (6-4mm2 ); Recommended Crimping Tool: T&B Sta-Kon ERG4002 or equivalent .
Temperature Re-Rating Curve

Time Current Curve